What is an FM 1-90 or 1-180 wind rating?

Direct Answer

FM 1-90 and FM 1-180 are wind-uplift ratings for tested commercial roof assemblies. They do not mean the roof can withstand 90 mph or 180 mph winds. The number refers to the uplift pressure, measured in pounds per square foot (psf), that the assembly withstands during FM testing.

The important distinction is that an FM 1-90 assembly is generally used where the calculated design uplift pressure is up to approximately 45 psf, while an FM 1-180 assembly corresponds to approximately 90 psf of design uplift, because FM’s rating incorporates a safety factor of 2.

For a commercial building, the required rating should not be selected simply because a roof is in a hurricane-prone area. The required wind uplift pressure depends on the building’s location, height, exposure, geometry, roof zone, and other design factors. The roof assembly must then be matched to the calculated pressures.

Who This Applies To

  • Commercial property owners
  • Developers and asset managers
  • General contractors
  • Architects and engineers
  • Facility managers
  • Commercial roofing contractors
  • Property managers reviewing roof specifications or submittals
  • Owners evaluating existing roof wind-uplift documentation

Not for: This explanation does not replace project-specific structural or wind-load calculations. The required roof assembly should be selected based on the applicable building code, project design calculations, manufacturer requirements, and the applicable FM approval listing.

1. What Does the “FM” Mean?

FM refers to FM Approvals, which evaluates and certifies specific building and roofing assemblies through standardized testing.

FM-rated roofing systems are commonly identified with designations such as:

  • FM 1-60
  • FM 1-75
  • FM 1-90
  • FM 1-120
  • FM 1-150
  • FM 1-180

These designations relate to the roof assembly’s tested wind-uplift resistance. FM 4474 provides the simulated wind-uplift testing methodology used for evaluating roof assemblies.

2. What Does the “1” Mean?

The “1” in FM 1-90 or FM 1-180 is not a wind-pressure value.

It refers to FM’s Class 1 roof classification. The second number is the important wind-uplift test value.

FM Rating Tested Uplift Pressure Approx. Design Uplift After 2× Safety Factor
FM 1-60 60 psf 30 psf
FM 1-90 90 psf 45 psf
FM 1-120 120 psf 60 psf
FM 1-150 150 psf 75 psf
FM 1-180 180 psf 90 psf

FM ratings therefore should not be interpreted as equivalent wind speeds. FM 1-90, for example, is a pressure-based rating and not a 90-mph rating.

3. What Does FM 1-90 Mean?

An FM 1-90 roof assembly has been tested to withstand 90 psf of simulated uplift pressure under the applicable FM testing methodology.

With FM’s safety factor of 2, the corresponding maximum design uplift pressure is approximately 45 psf.

That means an FM 1-90 assembly may be appropriate where the calculated design uplift requirement for the applicable roof zone does not exceed approximately 45 psf, assuming the complete FM-approved assembly is installed as listed.

4. What Does FM 1-180 Mean?

An FM 1-180 assembly has a tested uplift rating of 180 psf.

Applying the same 2× safety factor produces a corresponding design uplift pressure of approximately 90 psf.

Therefore, an FM 1-180 assembly provides substantially greater tested uplift capacity than an FM 1-90 assembly.

This does not mean every Florida commercial roof requires FM 1-180. The appropriate rating must be based on the calculated wind uplift pressures for the particular building and roof zones.

5. FM Ratings Are Not Wind-Speed Ratings

This is one of the most important points to understand.

FM 1-90 does not mean 90 mph.

FM 1-180 does not mean 180 mph.

Wind speed is one input used to calculate the forces acting on a building. Actual roof uplift depends on factors such as building geometry, height, exposure, internal pressure, roof zone, and other design conditions. IIBEC specifically notes that an FM rating is an uplift-pressure rating and should not be treated as a wind-speed equivalent.

6. Why Do Roof Corners Often Require Higher Ratings?

Wind pressure is not uniform across an entire roof.

Commercial roofs are commonly evaluated in different zones, including:

  • Field: the central portion of the roof
  • Perimeter: the roof area near the edges
  • Corner: areas subject to particularly high wind effects

Corner and perimeter areas can experience greater uplift than the field of the roof. FM’s RoofNav process accounts for different roof zones when determining required uplift pressures and identifying appropriate assemblies.

This is why a specification that simply says “FM 1-90 roof” may not provide enough information. The attachment requirements can vary between the field, perimeter, and corners.

7. The Rating Applies to the Entire Roof Assembly

An FM rating is not simply a rating for the membrane or metal panel.

The tested assembly can involve a specific combination of:

  • Roof deck
  • Insulation
  • Membrane or roof covering
  • Fasteners
  • Plates
  • Adhesives
  • Clips
  • Attachment spacing
  • Seam configuration
  • Other assembly components

Changing one of these components can mean the installed roof no longer matches the FM-approved assembly. FM listings therefore need to be checked for the exact configuration being proposed.

8. Why Is the Exact FM Assembly Important?

Consider a project specification calling for FM 1-90.

A contractor cannot necessarily use any combination of membrane, insulation, fasteners, and deck components and simply call the finished roof “FM 1-90.”

The actual installed configuration needs to correspond to an approved assembly.

This is particularly important during:

  • New commercial construction
  • Full roof replacement
  • Roof recover projects
  • Value-engineering proposals
  • Material substitutions
  • Fastener-spacing changes
  • Insulation changes
  • Roof-deck changes

9. FM Rating vs. ASCE 7 Wind Design

ASCE 7 and similar design standards are used to determine the wind pressures that a particular building and roof must resist.

The FM rating is then used to identify a tested roof assembly capable of meeting the required uplift performance.

In simplified terms:

  1. Determine the project’s applicable wind conditions.
  2. Calculate the roof uplift pressures.
  3. Evaluate the different roof zones.
  4. Determine the required roof-system resistance.
  5. Select an FM-approved assembly that meets the requirement.
  6. Install the assembly exactly as approved.

FM RoofNav can be used to identify assemblies based on project-specific wind conditions and roof characteristics. IIBEC notes that RoofNav considers factors including exposure, wind speed, roof dimensions, and wind-borne debris risk when determining pressures.

10. Why FM Ratings Matter in Florida Commercial Roofing

Florida commercial roofs can experience significant wind pressures, particularly in hurricane-prone areas.

A properly selected and installed wind-rated assembly can help address the roof’s resistance to wind uplift and provide documented evidence of the system’s tested performance.

However, the FM rating should not be used as a substitute for project-specific wind engineering. A higher rating is not automatically the correct rating; the assembly must match the calculated requirements and the applicable construction details.

11. What Should Owners Ask for in a Roofing Submittal?

When reviewing a commercial roofing proposal, owners and GCs should ask for the actual FM approval information rather than accepting a statement such as “FM rated.”

Useful documentation includes:

  • FM assembly number
  • FM uplift rating
  • Roof system manufacturer
  • Membrane or roof-covering type
  • Insulation configuration
  • Fastener and plate specifications
  • Attachment spacing
  • Roof deck type
  • Field, perimeter, and corner requirements
  • Applicable FM listing documentation

This allows the project team to verify that the proposed roof system actually corresponds to the required assembly.

12. What If a Contractor Says “FM 1-90 Roof”?

Ask for more information.

The statement by itself does not tell you:

  • Which FM assembly is being used
  • Whether the assembly matches the roof deck
  • What insulation configuration is included
  • What fastener pattern is required
  • Whether perimeter and corner enhancements are required
  • Whether substitutions have been made

The complete approved assembly should be reviewed rather than relying on the rating alone.

13. FM 1-90 vs. FM 1-180

Characteristic FM 1-90 FM 1-180
Tested uplift rating 90 psf 180 psf
Approx. design uplift after 2× safety factor 45 psf 90 psf
Wind speed rating? No No
Higher uplift capacity? Lower Higher
Automatically better for every building? No No
Must match an approved assembly? Yes Yes

14. Do Not Confuse FM Ratings With UL Ratings

FM and UL use different rating systems.

For example, FM 1-90 and UL Class 90 should not automatically be treated as equivalent ratings.

UL 580 uses its own test and classification system, while FM uses FM testing and approval procedures. The numbers therefore cannot simply be compared as if they represent the same test result.

15. What Should an Owner Do When Reviewing an Existing Roof?

If an existing commercial roof is documented as FM 1-90 or FM 1-180, verify the original assembly information where possible.

Review:

  • Original construction documents
  • Roofing specifications
  • Manufacturer information
  • FM approval documentation
  • Roof inspection reports
  • Repair records
  • Modification records
  • Replacement documentation

Also determine whether subsequent repairs or modifications have changed the roof from its originally approved configuration.

Bottom Line

FM 1-90 and FM 1-180 are commercial roof wind-uplift ratings, not wind-speed ratings. FM 1-90 represents a 90-psf tested uplift level and approximately 45 psf of design uplift after FM’s 2× safety factor. FM 1-180 represents a 180-psf tested level and approximately 90 psf of design uplift after the same safety factor.

The correct FM rating must be selected based on the building’s calculated wind pressures and roof zones. Most importantly, the rating applies to a specific tested roof assembly, not simply to a membrane, panel, or fastener. The exact FM-approved configuration should therefore be verified before accepting a commercial roofing submittal.

Related Questions

Sources

Last reviewed: October 2026

Related Resources

What Does a GC Need to Know About Manufacturer Warranty Inspections on a New Commercial Roof?

Need Commercial Roofing Help?

ShieldLine Roofing can help commercial owners, developers, and GCs evaluate roofing assemblies, wind-uplift requirements, installation details, and documentation for Florida commercial roofing projects.

Disclaimer: This information is provided for general educational purposes and is not structural, engineering, code-compliance, insurance, or design advice. Project-specific wind pressures and roof assembly requirements should be determined by the appropriate design professional and verified against the applicable building code, FM approval, manufacturer requirements, and project specifications.

New Construction Commercial Roofing

Rylee Hage - Founder of Shieldline Roofing

Meet the Founder: Rylee Hage

  • • Over 15 years of mastery in the roofing industry, bridging the gap between standard service and meticulous craftsmanship.
  • • Founded Shieldline Roofing on the principles of unwavering integrity and a profound commitment to protecting families.
  • • Dedicated to providing a personalized client experience built on a foundation of absolute trust.